Commercial & industrial

Can the site supply the battery charger and the factory at the same time?

The battery’s charging power is not the site’s spare import capacity. Review both before promising a fast overnight recharge.

Key point

Check charging against the site’s total import allowance and simultaneous loads. Confirm model-supported metering and control, then assess recharge time using the available headroom rather than the charger’s headline rating.

Look at the loads that stay on

An overnight charging window may still include refrigeration, ventilation or production. Give the designer interval load records and the approved supply limits. Ask for the expected total grid import while the battery charges, including the relevant phases, rather than checking charger power alone.

Make the limiting arrangement explicit

Ask which supported controller measures import and which device reduces charging when site demand rises. Have the installer confirm metering, settings and the response to lost communication. A feature on a related inverter is not proof that the quoted equipment will protect this site’s limit.

Put recharge time beside the limit

Request a charging estimate using the agreed import headroom, site loads and operating conditions. Keep the configured limit and acceptance checks in the handover record. Do not raise upstream protection settings to make an optimistic charging timetable fit; unresolved supply constraints belong with the designer.

Further reading: www.victronenergy.com · www.victronenergy.com

This article supports early project discussions. Final configuration depends on site conditions.

Email project details →Back to solutions